Form II, III and Form IV
Rating: 630Amp to 3200Amp
Front or Rear access type construction
Ample cabling space for easy connections
Top and bottom cable entry
Protection rating: IP 54 Ambient
temperature rating : 50°C
INCOMER: ACB – 3 or 4Pole, 630A to 3200A, 50 to 65kA, Fixed or draw out manual or motor operated.
MCCB – 3 or 4Pole, 630 to 1600A, 50kA, fixed or plug-in type, manual or motor operated.
BUS COUPLER: ACB or MCCB as above, Fixed or draw out, manual or motor operated.
MCCB – 3 or 4Pole, 630 to 1600A, 50kA, fixed or plug-in type, manual or
OUTGOINGS: ACB or MCCB as above, 3 or 4Pole, up to 1600A, 36 to 50kA.
BUS BAR: H.C.H.D. copper, tinned, insulated and color coded
ENCLOSURE: Electro galvanized sheet steel 2mm, powder coated, removable rear covers, extendable
on side
Rating: Up to 800Amp Ample cabling space for easy
connections Top, bottom and side cable entry
Protection rating: IP 65
Ambient temperature rating: 50°C
INCOMER: MCCB 100A to 800A, 3 Pole, 15 to 50kA, with / without external rotary handle.
OUTGOINGS: MCCB 30A to 630A, 15 to 50kA, 3 Pole
BUS BAR: H.C.H.D. copper, tinned, insulated and color coded
ENCLOSURE: Electro galvanized sheet steel, powder coated, suitable for floor or and wall mounting
With automatic PF regulator
With or without harmonic -filters
Standard sizes according to capacitor ratings
Stand alone units for safety purpose
Capacitor fitted with protection caps Temperature controlled
Standard fixing for increased air circulation Ambient temperature rating
INCOMER: Isolator or 40 to1250 Amp30 to 50 with /without external door handle
OUTGOING: HRC Fuses as per standard, 100 kA
BUS BARS: H.C.H.D. copper, tinned, rated for 50 kA short circuit
CONTACTORS: Special contactors rated according to the sizes of capacitors with damping resistance forthe inrush current
CAPACITORS: Equipped with advance technology capacitors for over voltage of 450V mounted in upright position
REGULATOR: Programmable microprocessor based PFR to allow compensation of low low line voltage.
Final DBs Flush or Surface mounted type
Assembled according to the specification
and requirements
Top, bottom and side cable entry
Ambient temperature rating 50’C
INCOMER: Isolator 40 to 160A, 3Pole or 4Pole with / without extended door handle
OUTGOINGS: ELCBs 25A to 125A, 30mA to 300mA, 2P/4Pole MCBs 6 to 63A, 1P/2P/3P, 6 to 10 kA
BUS BAR: 100/63Amp rated 1P/2P/3P/4P comb bus bar.
ENCLOSURE: Electro galvanized sheet steel, powder coated
INCOMER: MCCBs Fixed or Draw out type
OUTGOINGS: ELCBs, MCBs, Contactors, O/Ls,Motor Protection relays
CONTROLS: Programmable Logic Controls or Intelligent MP Relays Manual and Auto operations based withrelay or PLC controllers Power regulated with VFD / Soft Starters
INCOMER: Isolator or MCCB
OUTGOING: ELCBs, MCBs
BUS BARS: Load rated comb bus bar or rated insulated wires.
CONTACTORS: Special contactors rated according to the sizes of capacitors with damping resistance for the inrush current
CAPACITORS: Equipped with advance technology capacitors for over voltage of 450V mounted in upright position
REGULATOR: Programmable microprocessor based PFR to allow compensation of low
Application Standard : IEC 60439-1
Insulation Voltage : up to 690V AC
Rated Operational Voltage : 415V AC,3 Ph
Frequency : 50 Hz.
Bus bar Current : up to 250A
Bus bar Short Circuit : 36KA
Application : FCU, LIGHTING, & EF
Ambient temperature : 50°C
IP Protection : IP 41/54
Paint Color : RAL 7032 / 7035
Form of Construction : Form – I
Off-grid solutions – Roof top or Ground – based
standalone solutions designed to ensure energy
independence of residential and commercial sector to
reduce dependence on Public Electricity Grid. *Solar
Street & Highway Lighting *Solar Traffic Lights *Solar
Water Desalination *Solar Water Pumping *Solar Water
Treatment *Solar Water Heating
Based on customer’s demand we provide project initial
concept design through studying and observing on site.
Specification according to local authority specification
and regulations
Approved by Federal Electricity and Water Authority
Dept.GRP / Weather Proof GI metal enclosure as per
specified size